Compact manifolds up to 68.8 m³/h
1,600 kW at ΔT 20 K
Chamber size: | 300/200 |
Heating water throughput rate: | 68.8 m³/h |
Output at ∆T 20 K: | 1,600 kW |
Largest nozzle: | DN 125 |
Boiler connection: | up to DN 150 |
Uniform nozzle clearances: | 300 mm or 350 mm |
Operating pressure / Operating temperature: | max. 6 bar / max. 110°C |
Product description
Combined flow and return manifold, consisting of rectangular tube 300 x 200 mm, with chambers arranged adjacent to each other, separated by sinusoidal partition wall and made of black sheet steel S235. The compact manifold is pressure-tested and primed at the factory. Operating pressure max. 6 bar, operating temperature max. 110°C
- Nozzles as threaded and/or flanged connectors PN 6 / PN 16.
- All nozzles are aligned to the height of the shut-off valves and optionally available from the top, the side or the bottom.
- Drain connection couplings 1/2" for flow and return line chamber are a standard feature.
Configurator
Accessories
Stand bracket

For chamber size
| Bottom plate | Head plate | Adjustable in height |
---|---|---|---|
[mm] | [mm] | [mm] | [mm] |
120/80 to 160/80 |
150 x 150 | 120 x 120 | from 405 to 600 |
180/110 to 200/120 | 150 x 150 | 120 x 120 | from 270 to 340 |
280/180 to 700/500 | 200 x 200 | 150 x 180 | from 270 to 340 |
Soundproof and zinc-plated, consisting of bottom plate with stand pipe and head plate with guide pipe incl. connecting screws, adjustable in height.
Wall bracket

For chamber size
| Head plate |
Outreach up to manifold centre |
---|---|---|
[mm] | [mm] | [mm] |
120/80 to 160/80 |
120 x 120 | 220 |
180/110 to 200/120 | 120 x 120 |
300 |
280/180 to 700/500 | 150 x 180 |
500 |
Soundproof and zinc-plated, consisting of wall panel for screw fastening, bracket and head plate.
Thermal insulation

For chamber size
| PUR foam in coarse grain aluminium casing | PUR foam in galvanized sheet steel casing | Mineral wool in galvanized sheet steel casing |
---|---|---|---|
[mm] | [Insulation thickness in mm] | [Insulation thickness in mm] | [Insulation thickness in mm] |
120/80 to 200/120 |
45 | 45 | 100 |
280/180 to 300/200 | 50 | 50 | 100 |
400/200 to 700/500 | - | 60 | 100 |
In compliance with EnEV 2014 consisting of half shells with end pieces and cutouts for all nozzles.
Draining gutter

Made of galvanized sheet steel, size: 100/125/100 mm with 2" drain sieve
Fastening devices: Stand bracket, galvanized (height adaptable by customer), wall bracket, galvanized (max. outreach 200 mm)
Identification plate

Made of galvanized sheet steel with transparent cover for three-line label for screw fixing to the thermal insulation. Size: 100 x 50 mm, colours: red for flow line / blue for return line
Technical data
Heating water throughput rate
|
Output at
ΔT 20 K |
Manifold chamber
| Water quantity |
Heat transfer at 70°/50°C |
Return flow boost |
Wall thickness |
Weight (without nozzles and end caps) | |
---|---|---|---|---|---|---|---|---|
[m³/h] | [kW] | [Width / Height] | [l] | [kW] | [%] | [K] | [mm] | [kg/rm) |
68.8 | 1,600 | 300/200 | 54.1 | 8.3 | 0.5 | 0.1 | 6 | 51.3 |