Round-tube manifolds from 3.5 m³/h up to 1,085.0 m³/h
from 80 kW up to 25,320 kW at ΔT 20 K
Chamber size: | DN 50 up to DN 800 |
Heating water throughput rate: | 3.5 m³/h up to 1,085.0 m³/h |
Output at ∆T 20 K: | 80 kW up to 25,320 kW |
Nozzle clearance: | variable |
Operating pressure / Operating temperature: | as required |
Product description
One-chamber manifold / collector made of welded tube P235 in compliance with EN 10217, equipped with bumped ends on both sides. The one-chamber manifold is pressure-tested and primed at the factory. Operating pressure and operating temperature as required.
Available optional extras:
Higher operating pressures and temperatures, larger dimensions, other material (e.g. boiler tube in compliance with ADW4) as well as corrosion protection in compliance with AGI, work sheet Q 151.
- Nozzles as threaded and/or flanged connectors PN 6 up to PN 40.
- All nozzles are aligned to the height of the shut-off valves and optionally available from the top, the side or the bottom.
- Drain connection coupling 1/2" is a standard feature.
Accessories
Nozzles

Flanged connectors | Threaded connectors |
PN 10 / 16 | |
DN 15 | 1/2" |
DN 20 | 3/4" |
DN 25 | 1" |
DN 32 | 1 1/4" |
DN 40 | 1 1/2" |
DN 50 | 2" |
DN 65 | 2 1/2" |
DN 80 | 3" |
DN 100 | 4" |
DN 125 | |
DN 150 | |
Larger nozzles on request |
Stand bracket

Soundproof and zinc-plated, consisting of bottom plate with stand pipe and head plate with guide pipe incl. connecting screws, adjustable in height from 270 - 340 mm or 400 - 600 mm.
Wall bracket

Soundproof and zinc-plated, consisting of wall panel for screw fastening and bracket for manifold, outreach of 200 - 500 mm.
Thermal insulation

In compliance with EnEV 2014 consisting of: Thermal insulation for one-chamber manifolds
half shells with end pieces and cutouts for all nozzles
not diffusion-resistant.
- PUR foam in galvanized sheet steel casing
- Mineral wool in galvanized sheet steel casing
Draining gutter

Made of galvanized sheet steel, size: 100/125/100 mm with 2" drain sieve.
Fastening devices: Stand bracket, galvanized (height adaptable by customer), wall bracket, galvanized (max. outreach 200 mm)
Identification plate

Made of galvanized sheet steel with transparent cover for three-line label for screw fixing to the thermal insulation. Size: 100 x 50 mm, colours: red for flow line / blue for return line
Technical data
Dimension
|
Output at
ΔT 20 K | Throughput rate at flow velocity of 0.4 m / sec. | Output at ΔT 20 K | Throughput rate at flow velocity of 0.6 m / sec. |
Water quantity |
Wall thickness |
Weight (without nozzles and end caps) |
---|---|---|---|---|---|---|---|
[DN] | [kW] | [m³/h] | [kW] | [m³/h] | [litres/rm.] | [mm] | [kg/rm.] |
50 | 80 |
3.5 | 115 | 5.0 | 2.4 | 2.3 | 3.3 |
65 | 125 | 5.5 |
200 | 8.5 | 3.9 | 2.6 | 4.7 |
80 | 160 |
7.0 | 280 | 12.0 | 5.4 | 2.9 | 6.2 |
100 | 245 |
10.0 | 395 | 17.0 | 9.1 | 3.2 | 8.8 |
125 | 410 |
17.0 | 630 | 27.0 | 13.7 | 3.6 | 12.1 |
150 | 560 |
24.0 | 880 | 38.0 | 20.1 | 4 | 16.2 |
200 | 1,020 |
44.0 | 1,670 | 72.0 | 34.6 | 4.5 | 23.8 |
250 | 1,625 |
70.0 | 2,670 | 115.0 | 54.3 | 5 | 33.0 |
300 | 2,350 |
100.0 | 3,560 | 153.0 | 76.7 | 5.6 | 44.0 |
350 | 3,250 |
140.0 | 4,840 | 208.0 | 93.2 | 5.6 | 48.3 |
400 | 4,200 |
180.0 | 6,300 | 271.0 | 121.8 | 6.3 | 62.2 |
500 | 6,500 | 280.0 | 9,860 | 424.0 | 192.8 | 6.3 | 77.9 |
600 | 9,330 | 400.0 | 14,200 | 611.0 | 280.3 | 6.3 | 93.8 |
700 | 12,850 | 550.0 | 19,370 | 830.0 | 381.3 | 7.1 | 123.3 |
800 | 17,500 | 700.0 | 25,320 | 1,085.0 | 498.9 | 8 | 158.8 |