Rectangular-tube manifolds from 5.8 m³/h up to 243.0 m³/h
from 135 kW up to 5,652 kW at ΔT 20 K
Chamber size: | 80/60 up to 450/250 |
Heating water throughput rate: | 8.5 m³/h up to 243.0 m³/h |
Output at ∆T 20 K: | 135 kW up to 5,652 kW |
Nozzle clearance: | variable |
Operating pressure / Operating temperature: | max. 6 bar / max. 110°C |
Product description
One-chamber manifold / collector made of black sheet steel S235. The one-chamber manifold is pressure-tested and primed at the factory. Operating pressure max. 6 bar, operating temperature max. 110 °C.
Available optional extras:
Larger dimensions as well as corrosion protection in compliance with AGI, work sheet Q 151
- Nozzles as threaded and/or flanged connectors PN 6 aligned to the height of the shut-off valves.
- Nozzles optionally available from the top, the side or the bottom.
- Drain connection coupling 1/2" is a standard feature.
Accessories
Nozzles

Flanged connectors | Threaded connectors |
N 10 / 16 | |
DN 15 | 1/2" |
DN 20 | 3/4" |
DN 25 | 1" |
DN 32 | 1 1/4" |
DN 40 | 1 1/2" |
DN 50 | 2" |
DN 65 | 2 1/2" |
DN 80 | 3" |
DN 100 | 4 " |
DN 125 | |
DN 150 | |
Larger nozzles on request |
Stand bracket

Soundproof and zinc-plated, consisting of bottom plate with stand pipe and head plate with guide pipe incl. connecting screws, adjustable in height from 270 - 340 mm or 405 - 600 mm.
Wall bracket

Soundproof and zinc-plated, consisting of wall panel for screw fastening and bracket for manifold, outreach of 160 - 500 mm.
Thermal insulation
In compliance with EnEV 2014 consisting of:
Half shells with end pieces and cutouts for all nozzles
not diffusion-resistant.
- PUR foam in coarse grain aluminium casing
- PUR foam in galvanized sheet steel casing
- Mineral wool in galvanized sheet steel casing
Draining gutter

Made of galvanized sheet steel, size: 100/125/100 mm with 2" drain sieve.
Fastening devices: Stand bracket, galvanized (height adaptable by customer), wall bracket, galvanized (max. outreach 200 mm
Identification plate

Made of galvanized sheet steel with transparent cover for three-line label for screw fixing to the thermal insulation. Size: 100 x 50 mm, colours: red for flow line / blue for return line
Technical data
Manifold chamber
|
Output at
ΔT 20 K | Throughput rate at flow velocity of 0.4 m / sec. | Output at ΔT 20 K | Throughput rate at flow velocity of 0.6 m / sec. |
Water quantity |
Wall thickness |
Weight (without nozzles and end caps) |
---|---|---|---|---|---|---|---|
[Width / Height] | [kW] | [m³/h] | [kW] | [m³/h] | [litres/rm.] | [mm] | [kg/rm.] |
80/60 | 135 |
5.8 | 200 | 8.6 | 4.1 | 2.5 | 5.3 |
120/80 | 320 |
13.8 | 481 | 20.7 | 8.0 | 4 | 12.0 |
160/80 | 430 |
18.5 | 644 | 27.7 | 10.9 | 4 | 14.6 |
180/110 | 600 |
28.5 | 993 | 42.7 | 17.5 | 4 | 17.7 |
200/120 | 800 |
34.5 | 1,202 | 51.7 | 21.5 | 4 | 19.6 |
280/180 | 1,680 |
72.6 | 2,533 | 108.9 | 45.0 | 6 | 42.2 |
300/200 | 2,000 |
86.4 | 3,014 | 129.6 | 54.1 | 6 | 46.0 |
400/200 | 2,675 |
115.2 | 4,019 | 172.8 | 72.9 | 6 | 55.4 |
450/250 | 3,760 |
162.0 | 5,652 | 243.0 | 101.5 | 8 | 64.8 |