Product description
LegioNixx drinking water manifolds without dead zones to avoid the development of legionellae. Stainless steel manifolds in compliance with EN 10217-7 / DIN EN ISO 1127 TIG-welded, basin-pickled and passivated. Material 1.4571. Manifolds with concentric reductions at the ends and/or 90°bends directed upwards. The stainless steel manifolds are pressure-tested at the factory.
- Nozzles as connecting pieces (smooth ends for pressing), socket branches/threaded connectors or flanged connectors PN 10/16 aligned to the height of the shut-off valves
- Nozzles optionally available from the top, the side or the bottom
- Drain connection coupling 1/2" is a standard feature
This material is on the positive list of the Umweltbundesamt (note of transl.: German Federal Environmental Agency) and complies with the requirements of section 17 of the Trinkwasserverordnung (note of transl.: German Drinking Water Ordinance)
For applications outside the drinking water sector equipped with bumped ends on both sides.
Accessories
Nozzles

Flanged connectors | Threaded connectors / |
Connecting pieces |
PN 10 / 16 | Socket branches | with smooth ends |
DN 15 | 1/2" | 18.0 x 1.0 mm |
DN 20 | 3/4" | 22.0 x 1.2 mm |
DN 25 | 1" | 28.0 x 1.2 mm |
DN 32 | 1 1/4" | 35.0 x 1.5 mm |
DN 40 | 1 1/2" | 42.0 x 1.5 mm |
DN 50 | 2" | 54.0 x 1.5 mm |
DN 65 | 2 1/2" | 76.1 x 2.0 mm |
DN 80 | 3" | 88.9 x 2.0 mm |
DN 100 | 4 " | 108.0 x 2.0 mm |
Larger nozzles on request |
Stand bracket

Cold-insulated and zinc-plated, bottom plate with stand pipe and head plate with guide pipe incl. connecting screws, adjustable in height
Wall bracket

Cold-insulated and zinc-plated, wall panel for screw fastening and bracket with head plate, variable outreach, up to DN 125 with screw clamp.
Insulation for warm water applications

Consisting of:
Half shells with end pieces and cutouts for all nozzles
not diffusion-resistant
Draining gutter

Made of galvanized sheet steel. Size: 100 / 125 / 100 mm with 2" drain sieve
Fastening devices: Stand bracket, galvanized (height adaptable by customer), wall bracket, galvanized (max. outreach 200 mm)
Technical data
Throughput rate at flow velocity of 1.5 m/s
| Manifold pipe | Dimension |
Water quantity |
Wall thickness |
Weight (Pipe) |
---|---|---|---|---|---|
[m³/ h] | [DN] | [mm] | [litres/rm] | [mm] | [kg/rm] |
13.5 |
DN 50 |
60.3 x 2.0 | 2.5 | 2.0 | 2.9 |
22.1 |
DN 65 |
76.1 x 2.0 | 4.1 | 2.0 | 3.7 |
30.6 |
DN 80 | 88.9 x 2.0 | 5.7 | 2.0 | 4.3 |
50.5 |
DN 100 | 114.3 x 2.6 | 9.3 | 2.6 | 7.3 |
76.6 |
DN 125 | 139.7 x 2.6 | 14.2 | 2.6 | 8.9 |
112.8 |
DN 150 | 168.3 x 2.6 | 20.8 | 2.6 | 10.8 |
192.0 |
DN 200 | 219.1 x 3.0 | 35.6 | 3.0 | 16.2 |
302.0 |
DN 250 | 273.0 x 3.0 | 55.9 | 3.0 | 20.3 |