Cascade unit from 8.6 m³/h up to 34.4 m³/h

150 kW up to 600 kW at ∆T 15 K

Manifold / Collector pipe with low loss header

 

Chamber size: 120/80 up to 200/120
Heating water throughput rate: 8.6 m³/h up to 34.4 m³/h
Output at ∆T 15 K: 150 kW up to 600 kW
Nozzle clearance: variable
Product description

Manifold / Collector pipe for the accommodation of the boiler connections made of two section tubes on top of each other, material S235 with welded-in end caps and 1/2" drain connection couplings.
A low loss header is firmly attached as a unit to the manifold / collector pipe on the left-hand or right-hand side, depending on the type of installation. Fixed pedestal in standard design with an overall height of 200 mm. The cascade unit is pressure-tested at 9 bar and primed at the factory. Application range: Operating temperature up to max. 110°C, operating pressure up to max. 6 bar.
Low loss header made of hollow square profile S235 with two lateral nozzles for the connection of the secondary heating circuits.

  • Standard 1/2" coupling sleeves for emptying and sensor.
  • The heating boilers are connected by 90° pipe bends directed to the rear such that all boiler models and sizes can be installed.



Accessories

Special design

  • Angular design
  • U-shaped design
  • with flanged joint

Wall bracket

Soundproof and zinc-plated, consisting of wall panel for screw fastening and bracket.

Thermal insulation

Thermal insulation in compliance with EnEV 2014 consisting of two half shells each with end pieces and cutouts for all nozzles.

  • 40 mm PUR foam in coarse grain aluminium casing

Identification plate

Made of galvanized sheet steel with transparent cover for three-line label for screw fixing
to the thermal insulation. Size: 100 x 50 mm, colours: Red for flow line / blue for return line

 

Mounting frame

For free installation of wall-mounted condensing boilers,
matching the cascade unit.

2 heating boilers on each side
3 heating boilers on each side
4 heating boilers on each side

 

Technical data
Heating water throughput rate
Output at
ΔT 15 K
Manifold chamber
ConnectionArticle designation
[m³/h] [kW] [Width / Height]
   
8.6 150 120/80 Left-hand connection: Low loss header to the left of the manifold/collector with 2"-AG on secondary side (up to 8.6 m³/h)
      Right-hand connection: Low loss header to the right of the manifold/collector with 2"-AG on secondary side (up to 8.6 m³/h)
14.3 250 160/80 Left-hand connection: Low loss header to the left of the manifold/collector with 2"-AG on secondary side (up to 8.6 m³/h) or with flange DN 65, PN 6, on secondary side
(up to 14.3 m³/h)
      Right-hand connection: Low loss header to the right of the manifold/collector with 2"-AG on secondary side (up to 8.6 m³/h) or with flange DN 65, PN 6, on secondary side
(up to 14.3 m³/h)
34.4 600 200/120 Left-hand connection: Low loss header to the left of the manifold/collector with flange DN 80, PN 6 on secondary side (up to 21.8 m³/h) or with flange DN 100, PN 6, on secondary side
(up to 34.4 m³/h)
      Right-hand connection: Low loss header to the right of the manifold/collector with flange DN 80, PN 6 on secondary side (up to 21.8 m³/h) or with flange DN 100, PN 6, on secondary side
(up to 34.4 m³/h)